Hydronic Balancing is the process of optimising the distribution of water in a building’s heating or cooling system so it provides the intended indoor climate at optimum energy efficiency and minimal operating cost.
To provide the correct power output heating or cooling devices require a certain flow known as the design flow. Theoretically it is possible to design plants that deliver the design flow at each terminal unit (heating or cooling device). In reality this is not possible because pipes and valves only come in certain sizes and accurately predicting the real flow in a system is too complex. Some circuits (typically those closest to the pump) will be favoured by higher than required flows at the expense of other circuits that will have underflows.
In small heating systems (e.g. domestic systems) balancing is quite easy because of the small number of terminal units and relatively simple distribution network. Balancing can normally be achieved by simply pre-setting the flow through the radiators.
Larger buildings, such as offices or hospitals, have a more complicated heating and cooling system and require a more accurate balancing technique. To obtain a plant with the correct design flows, consultants design systems to include balancing valves, differential pressure controllers or pressure independent control valves. Balancing valves allow the measurement of differential pressures which can be used to calculate a flow. There are various balancing methods but all involve measuring differential pressures and adjusting them to the correct value by calculating what flow that represents. Differential pressure controllers are usually membrane- or spring driven valves that control the differential pressures in the installation. This will simplify balancing procedures and enable the installation to be more precisely controlled. Pressure independent valves combine the balancing and control functions in one valve and work based on springs and/or membranes to precisely control the flows in the distribution network and as such need no measuring or balancing procedure.
Contents |
In an unbalanced system there will always be favoured circuits that receive more water than they require. These favoured circuits steal flow from unfavoured circuits which will not then be able to provide the heating or cooling required. Control valves may temporarily help by gradually reducing the flow in favoured circuits, thus allowing unfavoured circuits to achieve the correct flow. This will however cause long delays in reaching the set temperature in the building after night setback and will make the installation very inefficient.
Balancing limits the flow in favoured circuits, forcing water through unfavoured circuits. As a result the required design flows are available to all circuits and the system can provide the required Indoor Air Quality. Avoiding overflows means the pump is not doing unnecessary work which saves energy, reduces operating cost and can reduce the size of the pump required (saves on initial pump investment). Balancing also saves energy and operating costs by reducing the amount of time between starting a plant and reaching the required indoor climate. For example, after every set back unbalanced plants must start earlier and run at maximum capacity for longer than balanced plants thereby using more energy.
Balancing an installation is a complicated and involved procedure because closing or throttling a valve will increase the flow in other parts of the installation. That is why a very structured procedure must be followed. The two most used methods are Compensated balancing and Proportional balancing. Both use an iterative methodology that will result in properly distributed flow in full load situation. The complicated nature of these balancing procedure is the reason that automatic solutions are gaining traction because it reduces or eliminates the need for complicated balancing procedures. Because of that differential pressure controllers and pressure independent valves are getting more and more popular.
The act of balancing can reveal common glitches such as wrongly mounted terminal units, damaged pipes, back-to-front check valves and blocked filters. These flaws are exposed while they can still be cheaply fixed. That is, before control equipment is commissioned, before ceilings are mounted, and most important, before tenants move in.
After several years use even the best-designed and best-built plants can suffer operational problems. A problem can have many causes: filters or valves may be clogged, terminal units and heat exchangers may have been replaced, a pipe may have been damaged during renovations, or a child's mischievous fingers may have left a shutoff valve half open. Balancing valves allow the measurement of differential pressure and temperature thereby pinpointing the cause of many such operational problems.